- Working condition : R410A, R407C, R22
- Suitable refrigerant : R410A, R407C, R22
- Ambient temperature : -30℃~+60℃ (electrity rate 50%)
- Fluid temperature : -30℃~+70℃ (electrity rate 50%)
- Ambient temperature : less than 95%RH
- Power : DC12V±10%, rectangle wave
- Action mode : 4-phase permanent-magnet step motor, straight moving wave
- Excitation system : 2-2 phase excitation, unipolar drive
- Excitation rate : 100~250 PPS
- Fluid direction : bi-flow
- Installation : Valve axis line is vertical in level surface within ±15°, coil up-ward
Spec code | (mm) | kW(U.S.R.T) |
DPF(0)1.3 | Φ1.3 | 5.28(1.5) |
DPF(0)2.0 | Φ2.0 | 8.8(2.5) |
DPF(0)2.4 | Φ2.4 | 10.56(3) |
DPF(0)3.2 | Φ3.2 | 17.6(5) |
DPF(0)5.2 | Φ5.2 | 28.1(8) |
DPF(0)6.4 | Φ6.4 | 35.5(10) |
Total pulse | Max.MOPD | Internal leakage | Max. working pressure(MPA) | Coil temp rise | Noise | Life |
2000 | > 2.26MPA (R22) : > 2.48MPA (R407C) : > 3.43MPA (R410) | < 600mL/min (Valve diameter <Φ2.4 )
< 1000mL/min (Valve diameter <Φ2.4) | 3.0MPa (R22) : 3.3MPa (R407C) : 4.2MPa (R410A) | < 60K | < 45dB(A) (300mm) | 5000 times |